Transformers & motors

Motor Current Estimator

Estimated motor current starts by converting mechanical output to electrical input using efficiency. Current then depends on voltage, phase, and power factor.

Estimate motor input current from mechanical output, voltage, phase, efficiency, and power factor.

Enter values

Calculated result

Estimated motor current

Calculating…

Calculated locally in your browser

Planning math only. Verify equipment specifications and installation requirements separately.

Motor current relationship diagramAn original simplified machine diagram paired with the current calculator result.RATING · VOLTAGE · LOADRESULTCalculated locallyFORMULA VISIBLEINPUTS EDITABLE
Motor Current Estimator relationship diagram. The illustration supports the text result; it is not a wiring or installation drawing.

What this calculator returns

Use the actual nameplate and governing design rules for installation work.

Formula and variables

The calculation runs entirely in your browser. Static formulas, definitions, examples, and tables remain readable without JavaScript.

Formula

Pinput = Pmechanical/efficiency; I = Pinput/(phase factor × V × PF).

P
Real or mechanical power, as identified by the calculator.
S
Apparent power in VA or kVA.
V
Winding, line, or load voltage.
I
Winding, line, or estimated input current.
PF
Entered power factor where real and apparent power differ.
η
Entered conversion or motor efficiency.

1 mechanical horsepower is 745.699872 W; phase factor is 1 or √3.

Worked example

Worked example inputs and result
InputValue
Power unitHorsepower
Mechanical output5 hp / kW
Voltage480 V
PhaseThree-phase AC
ResultA 5 hp, 480 V, three-phase motor at 90% efficiency and PF 0.85 is estimated at about 5.87 A.

A 5 hp, 480 V, three-phase motor at 90% efficiency and PF 0.85 is estimated at about 5.87 A.

Reference table

Nominal rating examples calculated from the ideal single-phase and balanced three-phase kVA-current equations. Verify real equipment ratings separately.
Apparent rating240 V single-phase480 V three-phase
1 kVA4.17 A at 240 V 1φ1.20 A at 480 V 3φ
5 kVA20.83 A at 240 V 1φ6.01 A at 480 V 3φ
10 kVA41.67 A at 240 V 1φ12.03 A at 480 V 3φ
25 kVA104.17 A at 240 V 1φ30.07 A at 480 V 3φ

Frequently asked questions

Is this motor-current result code compliant?

No. PowerTotals performs transparent electrical math and planning estimates. Installation decisions must be checked against equipment documentation, the adopted code, and the authority having jurisdiction.

Are my inputs uploaded?

No. Calculations run locally in your browser, and analytics never receives raw electrical values.

Assumptions and limitations

  • Not NEC full-load current and not a nameplate replacement.
  • No starting current, service factor, derating, protection, or conductor sizing.

Method and sources

Read the calculation methodology, review the technical sources, or browse the reference table index. Last reviewed .

Related calculators