Generator Sizing & Load Calculator

Generator sizing compares the running total, the largest single-start surge, and an entered reserve. The existing generator-load route now serves this sizing intent to avoid a duplicate page.

Size a generator estimate from running and starting loads, then apply your own reserve and power-factor assumptions.

Enter values

Advanced assumptions

Calculated result

Generator sizing totals

Calculating…

Calculated locally in your browser

Planning math only. Verify equipment specifications and installation requirements separately.

Generator sizing relationship diagramAn original simplified machine diagram paired with the current calculator result.RATING · VOLTAGE · LOADRESULTCalculated locallyFORMULA VISIBLEINPUTS EDITABLE
Generator Sizing & Load Calculator relationship diagram. The illustration supports the text result; it is not a wiring or installation drawing.

What this calculator returns

Compare both continuous and surge ratings, duration, derating, fuel, and manufacturer documentation.

Formula and variables

The calculation runs entirely in your browser. Static formulas, definitions, examples, and tables remain readable without JavaScript.

Formula

Running total = Σ(run W × qty); peak = running total + largest(start W - run W); reserve result = running × (1 + reserve).

P
Real or mechanical power, as identified by the calculator.
S
Apparent power in VA or kVA.
V
Winding, line, or load voltage.
I
Winding, line, or estimated input current.
PF
Entered power factor where real and apparent power differ.
η
Entered conversion or motor efficiency.

Starting watts are total starting demand per unit, not only the extra watts.

Worked example

Worked example inputs and result
InputValue
LoadsSee the example load list in the calculator
ResultA 700/2,200 W refrigerator and 1,050/2,150 W pump total 1,750 W running; the refrigerator creates the larger added surge, producing a 3,250 W single-start peak.

A 700/2,200 W refrigerator and 1,050/2,150 W pump total 1,750 W running; the refrigerator creates the larger added surge, producing a 3,250 W single-start peak.

Reference table

Nominal rating examples calculated from the ideal single-phase and balanced three-phase kVA-current equations. Verify real equipment ratings separately.
Apparent rating240 V single-phase480 V three-phase
1 kVA4.17 A at 240 V 1φ1.20 A at 480 V 3φ
5 kVA20.83 A at 240 V 1φ6.01 A at 480 V 3φ
10 kVA41.67 A at 240 V 1φ12.03 A at 480 V 3φ
25 kVA104.17 A at 240 V 1φ30.07 A at 480 V 3φ

Frequently asked questions

Is this generator load result code compliant?

No. PowerTotals performs transparent electrical math and planning estimates. Installation decisions must be checked against equipment documentation, the adopted code, and the authority having jurisdiction.

Are my inputs uploaded?

No. Calculations run locally in your browser, and analytics never receives raw electrical values.

Assumptions and limitations

  • Assumes one largest surge starts at a time.
  • No transfer switch, feeder, breaker, conductor, ventilation, or fuel-system sizing.

Method and sources

Read the calculation methodology, review the technical sources, or browse the reference table index. Last reviewed .